AMAT Applied Materials 0100-00991直流电源监控器模块
1.产 品 资 料 介 绍:
核心规格
功能与优势
安装与维护要点
AMAT Applied Materials 0100-00991直流电源监控器模块 英文资料:
AMAT 0100-00991 is a DC power monitor module designed by Applied Materials for semiconductor equipment DC power supply systems. It is used to monitor voltage, current, power, and battery status in real time, and trigger alarms and protections in case of abnormalities to ensure stable operation of the equipment.
Core specifications
Project specifications/characteristics remarks
Monitor parameters such as DC bus voltage, current, and power; Battery pack voltage, current, temperature; Partial models with expandable branch monitoring for insulation resistance
Input channel 2 DC incoming lines, 1 bus, 1 battery pack isolation measurement, accuracy ± 0.5%
Output control 4-channel DO (alarm, equalization/float charging, silicon chain regulation, battery current limiting) dry contact/transistor output
Alarm function: overvoltage, undervoltage, overcurrent, overheating, insulation degradation, battery abnormality sound and light alarm+remote reporting
Communication interface RS485 (Modbus RTU), CAN (optional) compatible with AMAT main control system
Power supply voltage DC 24-48 V (typical 24 V), redundant power supply optional
Working temperature 0-50 ℃ (expandable to 60 ℃) industrial grade environment
Size and weight approximately 147 × 51.5 × 114 mm, approximately 0.6 kg standard plug-in card
Apply wafer equipment, coating, etching, ion implantation and other DC power distribution to adapt to platforms such as Endura and Centura
Features and advantages
High precision measurement: supports 0.5% level voltage, current, and power monitoring to ensure power supply stability.
Intelligent battery management: automatic equalization/float charging switching, current limiting charging, temperature compensation, extending battery life.
Multiple protections: overvoltage, undervoltage, overcurrent, overheating, and insulation monitoring to prevent equipment damage.
Remote monitoring: RS485/CAN interface can be connected to AMAT or third-party dynamic environment systems to achieve centralized management.
Modular design: Standard plug-in card for easy maintenance and expansion.
Key points for installation and maintenance
install
Secure to the backplane slot to ensure good contact.
The power supply adopts redundant 24V DC with correct polarity.
Use shielded wires and ensure reliable grounding for input signals (voltage, current, insulation, battery).
Control the output to connect to alarm lights, charging modules, silicon chains, etc. according to their functions.
debug
Set measurement range, alarm threshold, communication address, and baud rate.
Check whether the measurement values of each channel are normal and whether the DO action is accurate.
Simulate fault verification alarm and protection functions.
AMAT Applied Materials 0100-00991直流电源监控器模块 产品展示
产品视频
3.其他产品
GJR2326500R1010 88VU01E模拟输出模块
GJR2390300R1010 81EA03B-E数码输出模块
GJR2365700R1010 88VA02B-E控制板总成
4.其他英文产品
ABB CM577-ETH communication module
ABB CM572-DP communication module
ABB 07KT97 H2 temperature measurement module
FAS-113DG | 531X133PROAG1 | F31X300CCHALG2 |
F46HSNA-R2-NS-NV-02 | 531X133PR0APG1 | F31X300CCHAKG2 |
F46HENA-R2-NS-NV-00 | 531X132APGACG1 | F31X300CCHAFG1 |
F46HEAA-R2-NS-NV-00 | 531X132APGAAG1 | F31X300CCHADG1 |
F46HCNA-R2-NS-NV-00 | 531X129SNCG1 | F31X300CCHAAG1 |
F46GENA-R2-NS-NV-00 | 531X129SNCADG1 | F31X210DMCACG1 |
The content is from Ruichang Mingsheng Automation Equipment Co., LTD
Contact: +86 15270269218